Page

Nonwoven Oven Exhaust Recovery with Heat Pipe (Case Study)

A nonwoven fabric plant exhausts 35,000 m3/h of oven air at about 160 C. EN159 recovered heat with a heat-pipe exchanger to preheat oven make-up air.

The Challenge

The oven needed hot make-up air. Exhaust at 160 C carried large heat. The stream carried fibre, so a robust separated recovery was needed.

Why Heat Pipe Air-to-Air Recovery

For hot, fibre-laden oven exhaust, a heat pipe gives separated-stream recovery with no rotating seal to foul. Rotary wheels are excluded where fibre load is high. Welded stainless plate is the alternative.

The EN159 Solution

EN159 heat-pipe modules, 35,000 m3/h, make-up air preheated from 25 C to 110 C, high-temperature alloy walls, 4 degree tilt, lint prefilter.

Measured Results

  • Recovered heat: about 0.8 MW
  • Make-up air preheated from 25 C to 110 C
  • Oven fuel cut by 23 percent
  • Estimated payback: 17 months

Compliance and Selection Notes

Heat-pipe recovery, separated streams, prefiltered. Rotary wheel excluded for fibre-laden duty.

Frequently Asked Questions

Why heat pipe at 160 C?

High-temperature alloy walls and matched fluid handle it; the pipe keeps streams separate from fibre.

Plate alternative?

Yes, welded stainless plate is offered where fibre load is lower.

Related Guides and Tools

Heat Pipe Heat Exchangers · Textile Stenter Heat Recovery · Industrial Waste Heat Recovery · Textile Heat Setting Plate · Contact EN159

Get a Site-Specific Recovery Estimate

Talk to an EN159 application engineer about your nonwoven oven exhaust stream. Call 15753355505 or visit our contact page for a site-specific recovery estimate.