Both an Energy Recovery Ventilator (ERV) and a Heat Recovery Ventilator (HRV) move energy from outgoing stale air to incoming fresh air without mixing the streams. The single thing that separates them is moisture: an HRV transfers only heat (sensible), while an ERV transfers both heat and humidity (enthalpy). That one distinction decides which you should specify.

What each one actually recovers

PropertyHRVERV
Transfers heatYesYes
Transfers moistureNoYes (partial)
Indoor humidity controlNone — humidity passes throughActive — balances supply/return humidity
Best climateCold, dry wintersHot/humid summers & mixed climates
Typical sensible effectiveness70–85%65–80%
Typical enthalpy effectivenessn/a55–75%

The cold-climate rule

In a heating-dominated climate, exhaust air is warm and humid (showers, cooking, breathing) while outdoor winter air is cold and bone-dry. An HRV recovers the heat but lets that indoor moisture escape — which is exactly what you want, because it stops the house from getting clammy. Adding an ERV in a cold climate can over-humidify the supply in winter unless the core is carefully balanced. So: cold and dry → HRV.

The humid-climate rule

In a cooling-dominated climate the problem flips. Outdoor summer air is hot and muggy; you do not want to import that humidity indoors. An ERV transfers a large share of the exhaust moisture back to the outgoing stream, pre-drying the supply and cutting both the load and the mould risk. So: hot and humid → ERV. See our enthalpy vs sensible guide for the physics.

Commercial and industrial: usually ERV

Offices, schools and labs run high internal moisture loads year-round. An ERV keeps humidity (and thus cooling demand) down, which usually pays back faster than an HRV despite the slightly lower sensible effectiveness. Use our ERV/HRV effectiveness calculator to compare the sensible and enthalpy numbers on your own conditions.

Cost and maintenance

An ERV core (typically a sorbent-coated plate or an enthalpy wheel) costs 10–30% more than a plain HRV plate and needs the same filter discipline. Neither should run without pre-filters — fouling kills effectiveness fast (see cleaning & maintenance).

Quick decision checklist